Insulated Electric Wire
Drop Wire for Pole Transformer(PDC, PDE)
22.9kV High Voltage Drop Insulated Wire for XLPE (PDC, PDE)
Range of application
Power cable used on the primary aspect of the pole transformer of high voltage overhead power line
Power cable used on the primary aspect of the pole transformer of high voltage overhead power line
Constitution
- Conductor : Hard-drawn copper wire or annealed copper wire for electrical application
- Semi-conductive layer : Semi-conductive XLPE
- Insulator : XLPE, PE
- Color of the insulator : Black
- Sheath:Black (Only for PDE)
- Product certifications : Standards of Hanmi
Conductor | Insulation Thickness |
Approx. Overall Diameter |
Conductor Resistance at 20℃ |
Test Voltage |
Standard Length |
|||
---|---|---|---|---|---|---|---|---|
Sectional Area |
No & Diameter of wire |
Outer Diameter |
||||||
mm2 | No/mm | mm | mm | Ω/km | kV | m | ||
- - - - 5.5 8 14 22 30 |
2.0 2.6 3.2 5.0 7/1.0 7/1.2 7/1.6 7/2.0 7/2.3 |
2.0 2.6 3.2 5.0 3.0 3.6 4.8 6.0 6.9 |
3.0 3.0 3.0 4.0 3.0 3.0 3.0 3.0 3.0 |
8.0 8.6 9.2 13.0 9.0 9.6 11.0 12.0 13.0 |
5.7 3.35 2.21 0.905 3.33 2.31 1.30 0.824 0.623 |
12 12 12 12 12 12 12 12 12 |
300 300 300 300 300 300 300 300 300 |
PDC |
5.5 | 7/1.0 | 3.0 | 4.0 | 14.6 | 3.33 | 12 | 300 | PDE |
60227 KS IEC 07
Single stranded vinyl insulation electric wire for 300/500V device wiring: 90℃
Range of application
It is a thermal resistant plasticizer added PVC insulated electric wire used mostly for general electric products or devices that use voltage of 300/500V.
It is a thermal resistant plasticizer added PVC insulated electric wire used mostly for general electric products or devices that use voltage of 300/500V.
Constitution
- Conductor : 1 grade (single-stranded) insulator
- Insulation material : PVC/E
- Color of the insulator : Black, white, red, green, yellow and blue
- Applicable specifications : KS C IEC60227-3
- Product certifications : Korean Industrial Standard(KS)
KS C IEC60227-3
Conductor | Insulation Thickness |
Mean Overall Diameter | Insulation Resistance |
Standard Length |
Test Voltage |
Approx. Weight |
|||
---|---|---|---|---|---|---|---|---|---|
Nominal Area | Class | Lower Limit | Upper Limit | ||||||
mm2 | - | mm | mm | mm | MΩ·km | m | kV | kg/km | |
1.5 2.5 |
1 1 |
0.7 0.8 |
2.6 3.2 |
3.2 3.9 |
12.1 7.41 |
0.011 0.009 |
2.5 2.5 |
20 40 |
60227 KS IEC 01
General use single-stranded vinyl insulated electric wire for 450/750V
Range of application
It is an insulated electric wire used mostly for external wiring with voltage of 450/750V and is characterized by good weather-resistance and durability.
It is an insulated electric wire used mostly for external wiring with voltage of 450/750V and is characterized by good weather-resistance and durability.
Constitution
- Conductor : Grade 1 (single-strand) or grade 2 (multiple-strand) conductor
- Insulation material : PVC/C
- Color of the insulator : Black, white, red, green, yellow and blue
- Applicable specifications : KS C IEC60227-3
- Product certifications : Korean Industrial Standard(KS)
KS C IEC60227-3
Conductor | Insulation Thickness |
Mean Overall Diameter | Insulation Resistance |
Standard Length |
Test Voltage |
Approx. Weight |
|||
---|---|---|---|---|---|---|---|---|---|
Nominal Area | Class | Lower Limit | Upper Limit | ||||||
mm2 | - | mm | mm | mm | MΩ·km | m | kV | kg/km | |
1.5 2.5 4.0 6.0 10 |
1 1 1 1 1 |
0.7 0.8 0.8 0.8 1.0 |
2.6 3.2 3.6 4.1 5.3 |
3.2 3.9 4.4 5.0 6.4 |
12.1 7.41 4.61 3.08 1.83 |
0.011 0.009 0.0085 0.0070 0.0070 |
2.5 2.5 2.5 2.5 2.5 |
20 40 50 70 120 |
|
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 |
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 |
0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.0 2.4 2.6 |
2.7 3.3 3.8 4.3 5.6 6.4 8.1 9.0 10.6 12.1 14.1 15.6 17.3 19.3 22.3 24.5 27.5 |
3.3 4.0 4.6 5.2 6.7 7.8 9.7 10.9 12.8 14.6 17.1 18.8 20.9 23.3 26.6 29.6 33.2 |
12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 |
0.010 0.009 0.0077 0.0065 0.0065 0.0050 0.0050 0.0043 0.0043 0.0035 0.0035 0.0032 0.0032 0.0032 0.0032 0.0030 0.0028 |
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 |
20 40 50 70 120 170 260 350 480 670 920 1160 1430 1780 2320 2930 3730 |
450/750 HFIX
450/750V 저독성 가교 폴리올레핀 절연전선
Range of application
It is halogen free polyolefin insulated electric wire used mainly as conductor for outdoor wiring for voltages below 450/750V with maximum allowed temperature of 90℃ for application.
It is halogen free polyolefin insulated electric wire used mainly as conductor for outdoor wiring for voltages below 450/750V with maximum allowed temperature of 90℃ for application.
Constitution
- Conductor : Grade 1 (single-strand) or grade 2 (multiple-strand) conductor
- Insulation material : Halogen free polyolefin
- Color of the insulator : Black, white, red, green, yellow and blue
- Applicable specifications : KS C 3341
- Product certifications : Korean Industrial Standard(KS)
KS C 3341
Conductor | Insulation Thickness |
Mean Overall Diameter | Insulation Resistance |
Standard Length |
Test Voltage |
Approx. Weight |
|||
---|---|---|---|---|---|---|---|---|---|
Nominal Area | Class | Lower Limit | Upper Limit | ||||||
mm2 | - | mm | mm | mm | MΩ·km | m | kV | kg/km | |
1.5 2.5 4 6 10 |
1 1 1 1 1 |
0.7 0.8 0.8 0.8 1.0 |
2.6 3.2 3.6 4.1 5.3 |
3.2 3.9 4.4 5.0 6.4 |
12.1 7.41 4.61 3.08 1.83 |
0.011 0.009 0.0085 0.0070 0.0070 |
2.5 2.5 2.5 2.5 2.5 |
20 40 50 70 120 |
|
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 |
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 |
0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.0 2.4 2.6 |
2.7 3.3 3.8 4.3 5.6 6.4 8.1 9.0 10.6 12.1 14.1 15.6 17.3 19.3 22.3 24.5 27.5 |
3.3 4.0 4.6 5.2 6.7 7.8 9.7 10.9 12.8 14.6 17.1 18.8 20.9 23.3 26.6 29.6 33.2 |
12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 |
0.010 0.009 0.0077 0.0065 0.0065 0.0050 0.0050 0.0043 0.0043 0.0035 0.0035 0.0032 0.0032 0.0032 0.0032 0.0030 0.0028 |
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 |
20 40 50 70 120 170 260 350 480 670 920 1160 1430 1780 2320 2930 3730 |
KIV450/750V PVC Insulated wire for Electrical Apparatus
Flexible single-stranded vinyl insulated electric wire for general application for voltage range of 450/750V (450/750V KIV)
Range of application
It is a flexible insulated electric wire used mainly for electrical devices that use voltage in the range of 450/750V.
It is a flexible insulated electric wire used mainly for electrical devices that use voltage in the range of 450/750V.
Constitution
- Conductor : Grade 5 (collective and composite multiple-strand)conductor
- Insulation material : PVC/C
- Color of the insulator : Black, white, red, green, yellow and blue
- Applicable specifications : KS C IEC 60227-3
- Product certifications : Korean Industrial Standard(KS)
KS C IEC 60227-3
Conductor | Insulation Thickness |
Mean Overall Diameter | Plain | Tinned | Insulation Resistance |
Approx. Weight |
Standard Length |
|||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Area | Class | Lower Limit | Upper Limit | |||||||
mm2 | - | mm | mm | mm | Ω/km | Ω/km | MΩ·km | kg/km | km | |
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 |
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 |
0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 |
2.8 3.4 3.9 4.4 5.7 6.7 8.4 9.7 11.5 13.2 15.1 16.7 18.6 20.6 23.5 |
3.4 4.1 4.8 5.3 6.8 8.1 10.2 11.7 13.9 16.0 18.2 20.2 22.5 24.9 28.4 |
13.3 7.98 4.95 3.30 1.91 1.21 0.780 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 |
13.7 8.21 5.09 3.39 1.95 1.24 0.795 0.565 0.393 0.277 0.210 0.164 0.132 0.108 0.0817 |
0.010 0.009 0.007 0.006 0.0056 0.0046 0.0044 0.0038 0.0037 0.0032 0.0032 0.0029 0.0029 0.0029 0.0028 |
30 40 50 80 130 180 280 370 500 700 970 1200 1490 1850 2440 |
200 200 100 100 100 100 100 100 100 100 100 100 100 100 100 |
OWOutdoor Weather Proof PVC Insulated Wire
600V outdoor vinyl insulated electric wire
Range of application
It is used for low-voltage overhead power line. This insulated electric wire with hard-drawn cable as conductor sheathed with PVC has outstanding weather resistance and durability.
It is used for low-voltage overhead power line. This insulated electric wire with hard-drawn cable as conductor sheathed with PVC has outstanding weather resistance and durability.
Constitution
- Conductor : Hard-drawn cable, hard-drawn multiple-strand cable for electrical application
- Insulation material : PVC
- Color of the insulator : Black
- Applicable specifications : KS C 3313
- Product certifications : Korean Industrial Standard(KS)
Single-strand conductor (Solid Conductor)
Conductor | Insulation Thickness |
Approx. Overall Diameter |
Conductor Resistance |
Test Voltage |
Tensile Load |
Approx. Weight |
Standard Length |
||
---|---|---|---|---|---|---|---|---|---|
Diameter | Sectional Area |
||||||||
mm2 | mm2 | mm | mm | Ω/km | V/1min | kg | kg/km | km | |
2.0 2.6 3.2 4.0 5.0 |
3.142 5.309 8.042 12.57 19.64 |
0.4 0.5 0.6 1.0 1.0 |
2.8 3.6 4.4 6.0 7.4 |
5.83 3.45 2.28 1.46 0.932 |
3,000 3,000 3,000 3,000 3,000 |
134.0 223.2 333.0 499.1 759.8 |
32 54 81 135 210 |
300 300 200 200 200 |
Multiple-strand conductor (Stranded Conductor)
Conductor | PVC Insulation Thickness |
Approx. Overall Diameter |
Conductor Resistance at 20℃ |
Test Voltage |
Tensile Load |
Approx. Weight |
Standard Length |
||
---|---|---|---|---|---|---|---|---|---|
Sectional Area |
No/mm No & Diameter of wire |
Outer Diameter |
|||||||
mm2 | No/mm | mm | mm | Ω/km | V/1min | kg | kg/km | km | |
8 14 22 30 38 50 60 80 100 |
7/1.2 7/1.6 7/2.0 7/2.3 7/2.6 19/1.8 19/2.0 19/2.3 19/2.6 |
3.6 4.8 6.0 6.9 7.8 9.0 10.0 11.5 13.0 |
0.6 1.0 1.2 1.2 1.4 1.4 1.4 1.5 1.5 |
4.8 6.8 8.4 9.3 11.0 12.0 13.0 14.5 16.0 |
2.41 1.35 0.849 0.642 0.502 0.394 0.313 0.237 0.185 |
3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 |
326 574 889 1,160 1,480 1,960 2,410 3,160 4,010 |
90 160 250 320 410 520 630 820 1,030 |
300 300 300 300 300 300 300 300 300 |
DVPVC Insulated Drop Wire
600V vinyl insulated electric drop wire
Range of application
It is generally used for overhead service line with voltage of less than 600V. With distinct coloring of each of the strands, it is convenient at the time of wiring with highly outstanding weather resistance of the sheathing. Therefore, it can be used safely for prolonged period of time wire fire or electrocution accident.
It is generally used for overhead service line with voltage of less than 600V. With distinct coloring of each of the strands, it is convenient at the time of wiring with highly outstanding weather resistance of the sheathing. Therefore, it can be used safely for prolonged period of time wire fire or electrocution accident.
Constitution
- Conductor : Hard-drawn cable for electrical application
- Insulation material : PVC
- Identification of cable strand : Coloring (2 Strands: Black and green / 3 Strands: Black, green and blue)
- Applicable specifications : KS C 3315
- Product certifications : Korean Industrial Standard (KS)
2-stranded Duplex (DV-2R)
Conductor | PVC Insulation Thickness |
Approx. Outer Diameter |
Conductor Resistance at 20℃ |
Test voltage | Min. Insulation Resistance MW·km |
Tensile Load |
Allowed current | Approx. Weight |
Standard Length |
||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Sectional Area |
No/mm No & Diameter of wire |
Outer Diameter |
|||||||||||
mm2 | No/mm | mm | mm | mm | W/km | Between conductor (in air) |
Between conductor (in water) |
20℃ | 60℃ | kgf | A | kg/km | m |
- - - 8 14 22 *30 38 *50 |
2.0 2.6 3.2 7/1.2 7/1.6 7/2.0 7/2.3 7/2.6 19/1.8 |
2.0 2.6 3.2 3.6 4.8 6.0 6.9 7.8 9.0 |
0.8 1.0 1.2 1.2 1.4 1.6 1.6 1.8 1.8 |
7.2 9.2 11.5 12.0 15.5 18.5 21.0 23.0 26.0 |
5.89 3.48 2.30 2.46 1.38 0.832 0.623 0.492 0.382 |
3000 3000 3000 3000 3000 4000 4000 4000 4000 |
1500 1500 1500 1500 2000 2000 2000 2500 2500 |
50 50 50 50 40 40 40 40 30 |
0.15 0.15 0.15 0.15 0.1 0.1 0.1 0.1 0.1 |
127 211 316 326 574 418 570 722 900 |
28 38 40 49 70 92 111 130 152 |
75 125 190 205 340 525 680 860 1100 |
300 200 200 300 300 300 300 300 300 |
3-stranded Duplex (DV-3R)
Conductor | PVC Insulation Thickness |
Approx. Outer Diameter |
Conductor Resistance at 20℃ |
Test voltage | Min. Insulation Resistance MW·km |
Tensile Load |
Allowed current | Approx. Weight |
Standard Length |
||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Sectional Area |
No/mm No & Diameter of wire |
Outer Diameter |
|||||||||||
mm2 | No/mm | mm | mm | mm | W/km | Between conductor (in air) |
Between conductor (in water) |
20℃ | 60℃ | kgf | A | kg/km | m |
- - - 8 14 22 *30 38 *50 |
2.0 2.6 3.2 7/1.2 7/1.6 7/2.0 7/2.3 7/2.6 19/1.8 |
2.0 2.6 3.2 3.6 4.8 6.0 6.9 7.8 9.0 |
0.8 1.0 1.2 1.2 1.4 1.6 1.6 1.8 1.8 |
7.8 9.9 12.5 13.0 16.5 20.0 22.0 25.0 28.0 |
5.89 3.48 2.30 2.46 1.38 0.832 0.629 0.492 0.382 |
3000 3000 3000 3000 3000 4000 4000 4000 4000 |
1500 1500 1500 1500 2000 2000 2000 2500 2500 |
55 55 55 55 45 45 45 45 35 |
0.2 0.2 0.2 0.2 0.15 0.15 0.15 0.15 0.15 |
127 211 316 326 574 418 570 722 900 |
25 34 44 43 62 62 97 113 133 |
115 190 285 310 510 785 1025 1290 1650 |
300 200 200 300 300 300 300 300 300 |